This MedLibrary.org supplementary page on Zone valve is provided directly from the open source Wikipedia as a service to our readers. Please see the note below on authorship of this content, as well as the Wikipedia usage guidelines. To search for other content from our encyclopedia supplement, please use the form below:

A zone valve is a specific type of valve used to control the flow of water or steam in a hydronic heating or cooling system.

In the interest of improving efficiency and occupant comfort, such systems are commonly divided up into multiple zones. For example, in a house, the main floor may be served by one heating zone while the upstairs bedrooms are served by another. In this way, the heat can be directed principally to the main floor during the day and principally to the bedrooms at night, allowing the unoccupied areas to cool down.

This zoning can be accomplished in one of two ways:

Contents

Zone valve construction and operation

Zone valves as used in home hydronic systems are usually electrically powered. In large commercial installations, vacuum or compressed air may be used instead. In either case, the motor is usually connected to the water valve via a mechanical coupling.

For electrical zone valves, the motor is often a small shaded-pole synchronous motor combined with a rotary switch that can disconnect the motor at either of the two stopping points ("valve open" or "valve closed"). In this way, applying power to the "open valve" terminal causes the motor to run until the valve is open while applying power at the "close valve" terminal causes the motor to run until the valve is closed. The motor is commonly powered from the same 24 volt ac power source that is used for the rest of the control system. This allows the zone valves to be directly controlled by low-voltage thermostats and wired with low-voltage wiring. This style of valves requires the use of an SPDT thermostat or relay.

Zone valves can also be constructed using wax motors and a spring-return mechanism. In this case, the valve is normally closed by the force of the spring but can be opened by the force of the wax motor. Removal of electrical power re-closes the valve. This style of zone valve operates with a perfectly ordinary SPST thermostat.

For vacuum- or pneumatically-operated zone valves, the thermostat usually switches the pressure or vacuum on or off, causing a spring-loaded rubber diaphragm to move and actuate the valve. Unlike the electrical zone valves, these valves automatically return to the default position without the application of any power, and the default position is usually "open", allowing heat to flow.

Highly sophisticated systems may use some form of building automation such as BACnet or LonWorks to control the zone valves.

Comparison with multiple circulator pumps

Multiple zones can be implemented using either multiple, individually-controlled circulator pumps or a single pump and multiple zone valves. Each approach has advantages and disadvantages.

Multiple Pump System

Advantages:

  • Simple mechanical and control design ("SPST thermostats")
  • Redundancy: If one zone pump fails, the others can remain working

Disadvantages:

  • Higher initial installation cost. Circulator pumps cost more than zone valves
  • Higher power consumption. Operating circulators draw substantial power any time the zone is actively heating. Zone valves, by comparison, draw little power at any time and many designs only draw power while in transition from open to close or vice-versa.

Zone Valve System

Advantages:

  • Lower initial installation cost.
  • Lower power consumption.

Disadvantages:

  • Zone valves can be unreliable. Zone valves operated by electric timing motors aren't "fail safe" (failing to the "open" condition).
  • No inherent redundancy for the pump. A zone-valved system is dependent upon a single circulator pump. If it fails, the system becomes completely inoperable.
  • The system can be harder to design, requiring both "SPDT" thermostats or relays and the ability of the system to withstand the fault condition whereby all zone valves are closed simultaneously.

Typical manufacturers of zone valves:

See also

Wikipedia content modification information:

  • This page was last modified on 19 November 2008, at 15:31.

Wikipedia Authorship and Review

Wikipedia content provided here is not reviewed directly by MedLibrary.org. Wikipedia content is authored by an open community of volunteers and is not produced by or in any way affiliated with MedLibrary.org.

Wikipedia Usage Guidelines

This article is licensed under the GNU Free Documentation License. It uses material from the Wikipedia article on "Zone valve".

The URL for this specific entry is:

All Wikipedia text is available under the terms of the GNU Free Documentation License. (See Copyrights for details). Wikipedia® is a registered trademark of the Wikimedia Foundation, Inc.